Product Resources
Links
Downloads
Share this Product
Description
- Compact design for side mounting on any enclosure surface where hot spot cooling or low capacity cooling is required.
- Closed loop cooling ensures clean enclosure air is recirculated without ever mixing with contaminated ambient air.
Standards
- Maintains enclosure's NEMA 12 rating
- IP 54
- UR, cUR and CE
Features
- R134a refrigerant.
- Thermostat control accessible from inside enclosure.
- Expansion valve increases efficiency with improved evaporator heat transfer and less frequent compressor operation.
- Continuous air circulation from high capacity fans.
- EMI/RFI suppression meets CE.
- Self-diagnostics on startup.
- Fault indication via LED light.
- Door contact for power down when enclosure door is opened.
- Gasket, mounting kit and template for cutout and drilling are included.
- Direct condensate discharge via 1/2" NPT threaded port.
Accessories
Part Details
Click Part No, below, for details (e.g., Product drawings, assembly instructions, ship weight)
Units shown: inch. Switch units to: mm
Overall Dimensions | Quantity | Price | Buy Now | |||
---|---|---|---|---|---|---|
Part No. | H | W | D | |||
DTS3041A115LG | 20.15 | 10.05 | 10.77 | 9 | $4,093.284 | Buy Now |
DTS3041A230LG | 20.15 | 10.05 | 10.77 | 4 | $4,173.075 | Buy Now |
DTS3041A460LG | 22.97 | 10.27 | 11.19 | 5 | Buy Now |
Electrical Data | DTS3041A115LG | DTS3041A230LG | DTS3041A460LG |
---|---|---|---|
Rated Voltage | 115 V 60 Hz | 230 V 50/60 Hz | 460 V 50/60 Hz |
Range of Operation | 103-127 V | 207-253 V | 360-506 V |
Power Consumption | 690 W | 663 W | 663 W |
Running Amps | 6.0 A | 4.1 A | 4.1 A |
Starting Current | 12.2 A | 10.4 A | 10.4 A |
Line Cord | Terminal Block | Terminal Block | Terminal Block |
Refrigeration Data | |
---|---|
Cooling Capacity BTU/h (Watts) +95/+95F +35/+35C | 2700 BTU/h (800 Watts) |
Type of Refrigerant | R134a |
Refrigerant Charge | 400 g |
Adjustable Control Range | +50F..+104F +10C..+40C Factory setting +95°F/+35C |
Max. Ambient Air Temp. | +114F (+45°C) |
Min. Ambient Air Temp. | +46°F (+8°C) |
Air Capacity (unrestricted) | Internal Circulation 191 CFM |
External Circulation 88 CFM | |
Condensation Discharge | Condensate Drain |
Filter Mat | Filterless |
Db Noise Level | <64 dB (A) |
Unit Weight | 51 lbs (23 kg) |
Exterior Case | Galvanized sheet metal |
Finish LG | RAL7035 light gray |
Finish GY | ANSI 61 Gray |
NEMA Rating | Enclosures IP 54/NEMA 12 |
Similar Products
Data subject to change without notice.
Tags: DTS, air conditioner, cooler, indoor, hot spot, low capacity, 3000 BTU, side mounting