Description
- Designed to use various water sources to cool enclosures where ambient conditions involve high temperatures, harsh conditions or are subject to frequent wash-down.
Standards
- UL, cUL, and CE
- Complies with
- NEMA 3R, 4, 4X
Features
- Compatible with chilled water/glycol, tower water and other circulated coolants
- Integrated thermostat & solenoid value with alarm contact provides automatic temperature control
- Rugged (10 bar) copper tube / aluminum fin heat exchanger with 1/2" barb connection
- Side, door or internal mounting provides complete installation flexibility
- Low noise, maintenance-free design
- Exterior case, galvanized steel construction finish RAL7035 Light Gray
Accessories
Part Details
Click Part No, below, for details (e.g., Product drawings, assembly instructions, ship weight)
Units shown: inch. Switch units to: mm
Part Number | H | W | D | Quantity | Price | Buy Now |
---|---|---|---|---|---|---|
PWS7102A115N4LG | 19.68 | 7.88 | 5.55 | 1 | $2,239.287 | Buy Now |
PWS7102A230N4LG | 19.68 | 7.88 | 5.55 | 1 | $2,239.287 | Buy Now |
PWS7102A115N4SS | 19.68 | 7.88 | 5.55 | |||
PWS7102A230N4SS | 19.68 | 7.88 | 5.55 | |||
PWS7332A115N4LG | 37.40 | 15.75 | 7.56 | 1 | Buy Now | |
PWS7332A230N4LG | 37.40 | 15.75 | 7.56 | |||
PWS7332A115N4SS | 37.40 | 15.75 | 7.56 | |||
PWS7332A230N4SS | 37.40 | 15.75 | 7.56 |
Electrical Data | PWS7102 | PWS7332 | Quantity | Price | Buy Now | ||
---|---|---|---|---|---|---|---|
Rated Voltage | 115 | 230 | 115 | 230 | |||
Frequency Hz | 60 | 50/60 | 60 | 50/60 | |||
Power Consumption | 95 w | 84 w | 453 w | 385 w | |||
Running Amps | 0.8 | 0.52 | 3.8 | 1.95 | |||
Connection | Terminal Block | Terminal Block |
Cooling Data | PWS7102 | PWS7332 | Quantity | Price | Buy Now |
---|---|---|---|---|---|
Cooling Capacity Enclosure +95F (+35C) Water +50F (+10C) | 3242 BTU/h (950W) | 10748 BTU/h (3140 W) | |||
Adjustable Control Range (Factory setting +95F ( +35C) | +46 to +122 F +8 to +50 C | +46 to +122 F +8 to +50 C | |||
Flow Rate at Rated Capacity | 53GPH 400L/h | 53 GPH 400 L/h | |||
Operting Pressure | 14.5 - 145 PSI 1 - 10 bar | 14.5 - 145 PSI 1 - 10 bar | |||
Ambient Air Temp | + 36/158 F +2/+70 C | + 36/158 F +2/+70 C | |||
Air Volume | 153 CFM 260 CM/h | 441 CFM 820 CM/h |
Data subject to change without notice.
Tags: air to water, heat exchanger, Type 3R, Type 4X, outdoor, closed loop, temperature, climate