Single Door Selection Guide

Type 4, 4X

Hammond Series 1447S EN4DCS all versions
ABB Controls

Disconnect
Switch

Flange operated switch (fusible or non-fusible)
Shaft: 8-12” dp enclosures, use DSFHS-12; 16” dp enclosures, use DSFHS-17
Handle: DSFHN-HS4 Handle: n/a
Door Hardware: n/a
Circuit
Breaker
Circuit breaker: ABB
Operating Mechanism: see ABB chart
Shaft: 8-12” dp enclosures, use K7FHD-S12; 16” dp enclosures, use K7FHD-S17
Handle: K7FHD-HS4 Handle: n/a
Door Hardware: n/a
 
Allen Bradley 1494U Flange Disconnect
Switch
Disconnect switch and operating mechanism: Bulletin 1494U
Handle: Bulletin 1494U-W1 Handle: n/a
Connecting rod: 8-10” dp enclosures, use 1494U-RA1; 12-16” dp enclosures, 
use 1494U-RA2
(except for Hammond part # 1447S46L12, use 1494U-RB2 (2))
Trailer fuse block kit (if required): Bulletin 1494U
Fuse kit (if required)
Line and load connectors (if required)
Door Hardware: n/a
1494U Flange Circuit Breaker Circuit breaker: C-H Westinghouse
Operating mechanism: Bulletin 1494U
Handle: Bulletin 1494U-W11 Handle: n/a
Connecting rod: 8-10” dp enclosures, use 1494U-RA1; 12-16” dp enclosures, 
use 1494U-RA2
Door Hardware: n/a
 
Cutler Hammer Type C361 Disconnect
Switch
Disconnect switch and operating mechanism
Handle: C361-H2 or H4 Handle: n/a
Door Hardware: n/a
Type C371
Circuit Breaker
Circuit breaker: C-H Westinghouse
Operating mechanism
Handle: 150 amp, use C371H2 or H4; 250-600 amp, use C371H6 or H8 Handle: n/a
Door Hardware: n/a
C-H Westinghouse Circuit Breaker w/FlexShaft Circuit breaker
Complete Flex-Shaft handle mechanism
Door Hardware: n/a
 
General Electric Type STDA
Flange
Disconnect
Switch
Disconnect switch Type QMR or QMW
Handle: STDA1X Handle: n/a
Fuse kit (if required)
Variable depth operating mechanism
Door Hardware: n/a
Type STDA
Flange
Circuit
Breaker
Circuit breaker
Handle: STDA1X Handle: n/a
Variable depth operating mechanism
Door Hardware: n/a
Circuit Breaker w/SpectraFlex Circuit breaker
Flange Mt. Handle: 150-600 amp, use STDA1X; SK1200, use STDA3X Handle: n/a
Breaker mounted mechanism.
Operating cable
Door Hardware: n/a
 
I-T-E Siemens Max-Flex
Flange
Disconnect
Switch
Disconnect switch: MCS
Fuse Kit (if required)
Handle: Flange mount FHOHS4 Handle: n/a
Switch operator mechanism
Operating cable (standard 36.0”)
Door Hardware: n/a
Max-Flex Flange Circuit Breaker Circuit breaker
Pressure wire connectors
Handle: Flange mount FHOH4 Handle: n/a
Circuit breaker operator mechanism
Operating cable: Standard 36"
Door Hardware: n/a
 
Square D Class 9422 Disconnect
Switch
Disconnect switch and operating mechanism 9422
Handle: 1447SN4 use A-1 or A-2; 1447SN4SS use A-2 Handle: n/a
Door Hardware: n/a
Class 9422
Circuit
Breaker
Circuit breaker
Operating mechanism: Class 9422
Handle: 1447SN4 use A-1 or A-2; 1447SN4SS use A-2 Handle: n/a
Door Hardware: n/a
Class 9422 “T” Disconnect
Switch w/ cable mechanism
Disconnect switch and operating mechanism 9422, Type T
Handle: 1447SN4 use A-1 or A-2; 1447SN4SS use A-2 Handle: n/a
Cable mechanism: Class 9422 CFT_O - 3, 5, or 10 foot
Door Hardware: n/a
Circuit Breaker w/cable mechanism Circuit breaker: Square D
Handle: 1447SN4 use A-1 or A-2; 1447SN4SS use A-2 Handle: n/a
Door Hardware: n/a

Space Occupied by Disconnect

Note: "K" = 8.62 when "C" = 8.00
  "K" = 11.62 when "C" = 12.00
  "P" = Wiring Space

Disconnects will occupy space on panel shown by dimensions "K", "L" and "M".

Wiring space "P" is available when disconnect is installed in the enclosure.

*The disconnect information and space occupied tables based on data supplied by disconnect manufacturer’s bulletins. Hammond Manufacturing not responsible for dimensional accuracy.


ABB Controls

ABB Controls Disconnect Switches (Flange Mounted Operators)

Fits Enclosure Depth ABB Switch 
Number
Amp   Fuse 
Class
Space Occupied When 
K=8.62
When 
K=11.62
8 12 Rating Fuse Clip L M P P
OETL-NF30-F 30A No Fuse 4.45 3.78 10.28 13.28
OETL-NF60-F 60A No Fuse 4.86 3.78 10.09 13.09
OETL-NF100-F 100A No Fuse 4.86 4.78 9.53 12.53
OETL-NF175-F 175A No Fuse 7.30 6.49 7.28 10.28
OETL-NF200-F 200A No Fuse 7.36 7.28 7.28 10.28
OESA-F30J6-F 30A 30A-600V J 4.28 6.58 8.61 11.61
OESA-F60J6-F 60A 60A-600V J 4.28 6.26 8.61 11.61
OESA-F100J6-F 100A 100A-600V J ¹ 6.54 7.65 8.17 11.17
      200A ²            

¹ J type fuse clips are standard. If 600 V Type “T” fuse clips are desired order T type fuse adaptor kit.
² 200 A available by using non-fusible 200A switch and a trailing fuse block. (consult ABB)

ABB Controls Circuit Breaker (Flange Mounted Operators)

Fits Enclosure Depth   Amp   Space Occupied When K=8.62 When K=11.62
8 12 ABB Mechanism Rating Fuse Type L M P P
FHD-M 150A D 6.92 3.94 9.17 12.17
FHF-M 15A-225A E/Q 5.98 4.23 7.72 10.72
FHF-M 225A Frame 7.44 4.23 7.72 10.72
  FHJ-M 400A J 9.71 5.62 8.77
  FHM-M 600A L 8.28 11.26 8.28
  FHM-M 800A M 10.11 11.26 7.87
 
Fits Enclosure Depth ISOMAX Circuit 
Breaker
Amp 
Rating
Operating 
Mechanism
Fuse 
Type
Space Occupied When 
K=4.75
When 
K=7.09
8 12 L M P P
S1N100TL 100A K2FHD-M S1 5.30 4.60 9.13 12.13
  S3N150TW 150A K3FHD-M S3 6.67 5.02   11.53
  S3N225TW 225A K3FHD-M S3 6.67 5.02   11.53
  S4N250BW 250A K4FHD-M S4 8.45 5.02   10.00
  S5N400TW 400A K5FHD-M S5 8.45 6.40   10.00
  S6N600TW 600A K6FHD-M S6 8.33 10.00   9.33
  S6N800TW 800A K6FHD-M S6 8.33 10.00   9.33

Charts reference Space Occupied by Disconnect Drawing.  

Allen Bradley

Allen Bradley 1494U Disconnect Switches
Fits Enclosure Depth Alan Bradley Amp     Space Occupied When 
K=8.62
When 
K=11.62
8 12 Type Number Rating Fuse Clip Fuse Class L M P P
DS30 30A No Fuse 3.88 6.62 6.75 9.75
DS30 30A 30A-250V H,K,R 5.25 6.62 6.75 9.75
DS30 30A 30A-600V H,K,R 8.00 6.62 6.75 9.75
DS30 30A 30A-600V J 5.25 6.62 6.75 9.75
DS30 30A 60A-250V H,K 6.00 6.62 6.75 9.75
DS30 30A 60A-600V H,K 8.50 6.62 6.75 9.75
DS30 30A 60A-600V J 5.38 6.62 6.75 9.75
DS60 60A No Fuse 3.88 6.62 6.62 9.62
DS60 60A 60A-250V H,K,R 6.00 6.62 6.62 9.62
DS60 60A 60A-600V H,K,R 8.50 6.62 6.62 9.62
DS60 60A 60A-600V J 5.38 6.62 6.62 9.62
DS60 60A 30A-600V H,K,R 8.00 6.62 6.62 9.62
DS60 60A 100A-250V H,K 8.50 6.62 6.62 9.62
DS60 60A 100A-600V H,K 10.50 6.62 6.62 9.62
DS60 60A 100A-600V J 7.25 6.62 6.62 9.62
DS100¹ 100A No Fuse 3.88 6.62 6.44 9.62
DS100¹ 100A 100A-250V H,K,R 8.12 6.62 6.44 9.62
DS100¹ 100A 100A-600V H,K,R 10.12 6.62 6.44 9.62
DS100¹ 100A 100A-600V J 6.88 6.62 6.44 9.62
DS100¹ 100A 60A-600V H,K,R 10.12 6.62 6.44 9.62
DS100¹ 100A 60A-600V J 8.88 6.62 6.44 9.62
  DS200¹ 200A No Fuse 4.75 7.88 8.12
  DS200¹ 200A 200A-250V H,K,R 10.88 7.88 8.12
  DS200¹ 200A 200A-600V H,K,R 13.38 7.88 8.12
  DS200¹ 200A 200A-600V J 9.50 7.88 8.12
  DS200¹ 200A 100A-600V H,K,R 12.00 7.88 8.12
  DS200¹ 200A 100A-600V J 8.75 7.88 8.12

Series B 
2 "M" dimension does not allow for auxiliary switches.  

Allen Bradley 1494U Circuit Breakers

Fits Enclosure Depth Allen Bradley
Type No.
Amp Rating Fuse Type Space 
Occupied
When 
K=8.62
When 
K=11.62
8 12 L M P P
M40 15A to 150A C-H Westinghouse Circuit Breakers
EHD,FD,FDB,FDC,HFD,HMCP
5.00 4.50¹ 8.12  
11.12
  M50 70A to 250A C-H Westinghouse Circuit Breakers
JD,JDB,JDC,HJD,HMCP
9.75 4.75¹  
10.62
  M60 100A to 400A C-H Westinghouse Circuit BreakersKD,KDB,DK,HKD,HMCP 9.69 6.12¹  
10.50

1 "M" dimension does not allow for auxiliary switches. 
Charts reference Space Occupied by Disconnect Drawing.
 

Cutler Hammer

Cutler Hammer C361 Disconnect Switches

Fits Enclosure Depth Cutler Hammer Amp     Space Occupied When 
K=8.62
When 
K=11.62
8 12 Type Number Rating Fuse Clip Fuse Class L M P P
C361NC 30A No Fuse 5.75 7.43 7.31 10.31
C361SC21 30A 30A-250V H, K, R 8.38 7.43 7.31 10.31
C361SC61 30A 60A-250V H, K, R 8.38 7.43 7.31 10.31
C361SC61 30A 30A-600V H, J, K, R 8.38 7.43 7.31 10.31
C361ND 60A No Fuse 5.75 7.43 7.31 10.31
C361SD22 60A 60A-250V H, K, R 8.38 7.43 7.31 10.31
C361SD22 60A 30A-600V J 8.38 7.43 7.31 10.31
C361SD62 60A 30A-600V H, K, R 8.38 7.43 7.31 10.31
C361SD62 60A 60A-600V J 8.38 7.43 7.31 10.31
C361NE 100A No Fuse 5.56 8.95 7.47 9.91
C361SE263 100A 100A-250V H, K, R 10.31 8.95 7.47 9.91
C361SE263 100A 100A-600V H, K, R 10.31 8.95 7.47 9.91
C361SE263 100A 100A-600V J 10.31 8.95 7.47 9.91
¹ , ² ² C361NF 200A No Fuse 13.06 10.00 4.94 7.94
¹ , ² ² C361SF264 200A 200A-250V H, K, R 13.06 10.00 4.94 7.94
¹ , ² ² C361SF264 200A 200A-600V H, J, K, R 13.06 10.00 4.94 7.94
¹ Wire bend space "P" does not allow the use of maximum cable size in 8" deep enclosures.
² 200A switch should be installed in enclosures with an "A" dimension of 30" or greater.   Cutler Hammer C371 Circuit Breaker Operators (C-H Westinghouse Circuit Breakers)
Fits Enclosure Depth Allen Bradley Type No. Amp   Space Occupied When K=8.62 When K=11.62
8 12 Rating Fuse Type L M P P
C371E 150A F Frame EHD,FDB,FD,HFD,FDC 6.00 5.50 8.44 11.44
C371E 150A F Frame HMCP 6.00 5.50 8.44 11.44
  C371F 250A J Frame JDB,JD,HJD,JDC 8.94 8.00 11.25
  C371F 250A J Frame HMCP 10.94 8.00 11.25
  C371F 400A K Frame DK,KDB,KD,HKD 9.75 8.00 10.75
  C371F 400A K Frame HMCP 9.75 8.00 10.75
  C371G 600A L Frame LD,HLD,LDC 8.44 11.88 9.18
  C371G 600A L Frame HMCP 8.44 11.88 9.18
Charts reference Space Occupied by Disconnect Drawing.   Cutler Hammer Flex-Shaft™ Operator Mechanisms (C-H Westinghouse Circuit Breakers)
Fits Enclosure Depth Complete Operator   Breaker Height Breaker Width
8 12 Mechansim Amp Rating Fuse Type "X" "Y"
F1S03 150A F Frame EHD,FDB,FD,HFD,FDC 6.00 4.12
F1S03 150A F Frame HMCP 6.00 4.12
F2S03 250A J  Frame JDB,JD,HJD,JDC 10.00 4.12
F2S03 250A J  Frame HMCP 10.00 4.12
F3S03 400A K  Frame DK,KDB,KD,HKD 10.12 5.50
F3S03 400A K  Frame HMCP 12.45 5.50
  F4S04 600A L  Frame LD,HLD,LDC 10.75 8.25
  F7S04 800A M Frame MD,MDS 16.00 8.25
  F5S04 1200A N Frame ND,HND,NDC 16.00 8.25
  F6S04 2500A R Frame RD,CRD, RDC 16.00 15.50
  • F,J,K frame Flex-Shafts™ available in 3' to 10' lengths.
  • L,N,R frame Flex-Shafts™ available in 4' to 6' lengths.
  • Overall (Height "X" and Width "Y")
  • Minimum wire bend space (manufacturer specified)
  • Location "M" from right to left.

Charts reference Space Occupied by Disconnect Drawing.

General Electric

General Electric Type STDA Disconnect Switches

Fits Enclosure Depth General Electric 
Mechanism For 
Switch
Amp 
Rating
    Space Occupied When 
K=8.62
When 
K=11.62
8 12 Fuse Clip Fuse Class L M P P
TDOM1A 30A No Fuse 7.75¹ 5.25 9.12 12.12
TDOM1A 30A 30A-250V H, R 7.75¹ 5.25 9.12 12.12
TDOM1B 30A 30A-600V H, R 12.38¹ 5.25 9.12 12.12
TDOM1B 30A 60A-250V H, R 12.38¹ 5.25 9.12 12.12
TDOM1B 30A 60A-600V H, R 12.38¹ 5.25 9.12 12.12
TDOM1A 60A No Fuse 7.75¹ 5.25 9.12 12.12
TDOM1B 60A 60A-250V H, R 12.38¹ 5.25 9.12 12.12
TDOM1B 60A 60A-600V H, R 12.38¹ 5.25 9.12 12.12
TDOM1B 60A 100A-250V H, R 12.38¹ 5.25 9.12 12.12
TDOM1B 60A 100A-600V H, R 12.38¹ 5.25 9.12 12.12
TDOM1A 100A No Fuse 7.75¹ 5.25 9.12 12.12
TDOM1B 100A 100A-250V H, R 12.38¹ 5.25 9.12 12.12
TDOM1B 100A 100A-600V H, R 12.38¹ 5.25 9.12 12.12
TDOM1B 100A 200A-250V H, R 12.38¹ 5.25 9.12 12.12
TDOM1B 100A 200A-600V H, R 12.38¹ 5.25 9.12 12.12
TDOM2 200A No Fuse 7.00 9.12 6.50 9.50
TDOM2 200A 200A-250V H, R 15.38 9.12 6.50 9.50
TDOM2 200A 200A-600V H, R 15.38 9.12 6.50 9.50
¹ Applies to 8" deep enclosures, and is 0.875" less in 12" deep enclosures.       General Electric Type STDA Circuit Breaker Operators
Fits Enclosure Depth General Electric 
Mechanism For 
Switch
Amp Rating   Space Occupied When 
K=8.62
When 
K=11.62
8 12 Fuse Type L M P P
SDOM1A 150A TEB, TED, THED 7.75¹ 5.25 9.06 12.06
SDOM1A 150A TEC 7.75¹ 5.25 9.06 12.06
TDOM1B 150A TB1 12.38¹ 5.25 9.06 12.06
TDOM1B 150A TEC, TECL 12.38¹ 5.25 9.06 12.06
TDOM1C 150A TEL 7.75¹ 5.25 9.06 12.06
TDOM1D 150A THLC1 7.75¹ 5.25 6.62 9.62
TDOM3 225A TFJ 10.38 5.75 7.62 10.62
TDOM3 225A TFK, THFK, TFL 10.38 5.75 7.62 10.62
TDOM4 400A TJJ, TJK4, THJK4, TJL4V 8.25 9.38 6.69 9.69
TDOM4 600A TJK6, THJK6, TJ4V, TJL4V 8.25 9.38 6.69 9.69
TDOM5 400A TB4, TJH6S 14.25 9.38 6.69 9.69
TDOM6 225A TLB2, THLC2 11.75 9.38 6.12 9.12
TDOM6 400A TLB4, THLC4 11.75 9.38 4.75 7.75
SDOM1A 150A SPECTRA SE150 7.75¹ 5.25 9.06 12.06
SDOM3 250A SPECTRA SF250 10.38 5.75 7.06 10.06
  SDOM4 600A SPECTRA SG600 10.00 7.00 7.93
¹ Applies to 8" deep enclosures, and is 0.875" less in 12" deep enclosures.
Charts reference Space Occupied by Disconnect Drawing.       General Electric Circuit Breakers (Spectra-Flex™ Cable Operators)
Fits Enclosure Depth     Circuit Breaker Height Circuit Breaker Width
C=8 C=12 Frame Size Max Amp Rating X Y
E150 150A 6.31 4.12
SE150 150A 6.31 4.12
  SF250 250A 10.12 4.12
  SG600 600A 10.09 5.50
  SK1200 1200A 15.50 8.25
 
Frame Size Breaker Mechanism Flange Mounting Handle¹ Operating Cable²
E150 SCOM1A SCH1 SC3L
SE150/SF250 SCOM1EF SCH1 SC3L
SG600 SCOM1G SCH1 SC3L
SK1200 SCOM1K SCH2K SC3H
¹ Operating Cables are available 3' to 10' lengths. In the table above, the number "3" in the part number indicates a 3' cable.
Siemens I-T-E 

I-T-E - Disconnect Switches (Max-Flex™ Operators)
Fits Enclosure Depth   Amp 
Rating
    Disconnect Height 
"X"
Disconnect Width 
"Y"
C=8 C=12  Switch Fuse Clip Fuse Class
MCS603R 30A No Fuse 5.52 6.13
MCS603R 30A 30A-250V H,K,R 8.11 6.13
MCS603R 30A 30A-600V H,K,R 10.11 6.13
MCS603R 30A 30A-600V J 8.48 6.13
MCS606R 60A No Fuse 5.52 6.13
MCS606R 60A 60A-250V H,K,R 7.86 6.13
MCS606R 60A 60A-600V H,K,R 10.38 6.13
MCS606R 60A 60A-600V J 8.36 6.13
MCS610R 100A No Fuse 7.59 7.38
MCS610R 100A 100A-250V H,K,R 11.85 7.38
MCS610R 100A 100A-600V H,K,R 13.85 7.38
MCS610R 100A 100A-600V J 10.60 7.38
MCS620R 200A No Fuse 9.00 9.17
MCS620R 200A 200A-250V H,K,R 14.70 9.17
MCS620R 200A 200A-600V H,K,R 17.20 9.17
MCS620R 200A 200A-600V J 13.32 9.17
Siemens I-T-E Max-Flex™ Operators (Circuit Breakers)
Complete Operator Mechansim   Breaker
Frame
Size
Circuit Breaker Type Circuit
Breaker Height
"X"
Circuit Breaker 
Width
"Y"
Amp Rating
FHOE036 125A ED ED2,ED4,ED6,HED4,HED6, 6.34 3.00
FHOE036 125A CED CED6 9.58 3.00
FHOF036 250A FD FXD6-A,FD6-A,HFD6,FXD6-ETJ,HHFD6, HHFXD6 9.50 4.50
FHOF036 250A CFD CFD6,CFD6-ETI 14.25 4.50
FHOJ036 400A, 600A JD, LD JXD2,LXD6,JD6,LD6,HJD6,HLD6,HHJD6,HHLD6, HHJXD6,HHLXD6,JXD6-ETI,LXD6-ETI 11.00 7.50
FHOJ036 400A, 600A CJD,CLD CJD6,CLD6,CJD6-ETI,CLD6-ETI 17.86 7.50
FHOLMO36 800A LMD LMD6,LMXD6,HLMD6,HLMDX6,LMXD6-ETI 16.00 9.00
Last three digits of operator mechanism part number denote cable length in inches.
48" cables are offered for ED,FD,JD/LD operators
Square D

Square D Class 9422 Disconnect Switches
Fits Enclosure Depth   Amp 
Rating
    Space Occupied When 
K=8.62
P
When 
K=11.62
P
8 12 Square D Type Number Fuse Clip Fuse Class L M
TCN-30 30A No Fuse 3.80 6.84 7.56 10.56
TCF-30 30A 30A-250V H, K, R 5.53 6.84 7.56 10.56
TCF-33 30A 30A-600V H, K, R 8.15 6.84 7.56 10.56
TCF-33 30A 60A-250V H, K, R 6.15 6.84 7.56 10.56
TCF-33 30A 30A-600V J 5.53 6.84 7.56 10.56
TDN-60 60A No Fuse 3.80 6.84 7.56 10.56
TDF-60 60A 30A-600V H, K, R 8.15 6.84 7.56 10.56
TDF-60 60A 60A-250V H, K, R 6.15 6.84 7.56 10.56
TDF-63 60A 60A-600V H, K, R 8.65 6.84 7.56 10.56
TDF-63 60A 60A-600V J 5.53 6.84 7.56 10.56
  TEN-10 100A No Fuse 3.80 6.84 7.44 10.44
  TEF-10 100A 100A-250V H, K, R 8.25 6.84 7.44 10.44
  TEF-10 100A 100A-600V H, K, R 10.25 6.84 7.44 10.44
  TEF-10 100A 100A-600V J 7.05 6.84 7.44 10.44
TC-1 30A No Fuse 5.75 6.00 6.62 9.62
TC-2 30A 30A-250V H, K, R 5.75 6.00 6.62 9.62
TC-3 30A 30A-600V H, K, R 7.75 6.00 6.62 9.62
TC-3 30A 60A-250V H, K, R 5.88 6.00 6.62 9.62
TC-3 30A 30A-600V J 5.75 6.00 6.62 9.62
TD-1 60A No Fuse 6.38 6.62 7.50 10.50
TD-2 60A 30A-600V H, K, R 8.50 6.62 7.50 10.50
TD-2 60A 60A-250V H, K, R 6.50 6.62 7.50 10.50
TD-3 60A 60A-600V H, K, R 9.00 6.62 7.50 10.50
TD-3 60A 60A-600V J 6.38 6.62 7.50 10.50
  TE-1 100A No Fuse 4.75 8.38 10.25
  TE-2 100A 100A-250V H, K, R 7.50 8.38 10.25
  TE-2 100A 100A-600V H, K, R 9.50 8.38 10.25
  TE-2 100A 100A-600V J 6.25 8.38 10.25
  TE-3 100A 200A-600V J 13.75 8.38 10.25
  TF-1 200A No Fuse 5.50 11.62 8.88
  TF-2 200A 200A-250V H, K, R 11.50 11.62 8.88
  TF-2 200A 200A-600V H, K, R 14.00 11.62 8.88
  TF-2 200A 200A-600V J 10.12 11.62 8.88
  TF-3 200A 400A-600V J 14.50 11.62 8.88

Square D Class 9422 Variable Depth Operators (Circuit Breakers)

Fits Enclosure Depth General Electric 
Mechanism For 
Switch
Amp 
Rating
  Space Occupied When 
K=8.62
P
When 
K=11.62
P
8 12 Frame Size L M
RG-1 75A GJL 3.53 3.74 7.47 10.47
RG-1 100A GJL 3.53 3.74 7.47 10.47
RN-1 100A FAL,FHL 5.12 5.25 7.62 10.62
RP-1 250A KAL,KHL 7.12 5.62 8.38 11.38
  RR-1 400A LAL, LHL, Q4L 7.62 8.75 7.00
Charts reference Space Occupied by Disconnect Drawing.       Square D Class 9422 Disconnect Switches (Cable Mechanism 9422-CFT30 and 9422A-1 Handle Mechanism)
Fits Enclosure Depth Square D Type 
Number
Amp 
Rating
    Disconnect Height 
"X"
Disconnect Width
"Y"
C=8 C=12 Fuse Clip Fuse Class
TCN-30 30A No Fuse 5.90 6.20
TCF-30 30A 30A-250V H, K, R 7.50 6.20
TCF-33 30A 30A-600V H, K, R 10.15 6.20
TCF-33 30A 60A-250V H, K, R 8.15 6.20
TCF-33 30A 30A-600V J 7.50 6.20
TDN-60 60A No Fuse 5.90 6.20
TDF-60 60A 30A-600V H, K, R 10.15 6.20
TDF-60 60A 60A-250V H, K, R 8.15 6.20
TDF-63 60A 60A-600V H, K, R 10.65 6.20
TDF-63 60A 60A-600V J 7.50 6.20
  TEN-10 100A No Fuse 5.90 6.20
  TEF-10 100A 100A-250V H, K, R 10.35 6.20
  TEF-10 100A 100A-600V H, K, R 12.35 6.20
  TEF-10 100A 100A-600V J 10.35 6.20
      Square D Class 9422 Cable Mechanism (Circuit Breakers)
Fits Enclosure Depth   Amp   Circuit Breaker Circuit Breaker
C=8 C=12 Cable Type Switch Rating Frame Type Height "X" Width "Y"
9422 CGJ30 75A GJL 4.75 3.50
9422 CEJ30 100A GJL 4.75 3.50
9422 CFA30 100A FAL,FHL 6.00 4.50
9422 CKA30 250A KAL,KHL 8.00 4.50
  9422 CLA30 400A LAL,LHL,Q4L 11.00 6.00
Use cable mechanism with circuit breaker and 9422-A1 handle mechanism
Cable operators are offered in 3’, 5’, and 10’ lengths. Last 2 digits of part numbers above (30) are for 3’ cables

Space Occupied By Disconnect Switch
1. Square D Cable System permits circuit breaker locations separate from flange mounted handle mechanism.
2. See National Electrical Code 2005 article 430-10(b) for wiring space (Ref "P") needed for line side conductors.
3. Select cable mechanism length based on disconnect location in enclosure. See Square D instructions for minimum cable bend radius.
4. Space occupied by circuit breaker is calculated by:

  • Overall (Height "X" and Width "Y")
  • Minimum wire bend space (manufacturer specified)

Charts reference Space Occupied by Disconnect Drawing.