Multi-Door Selection Guide

UHD

ABB Controls
Disconnect switch:
  • Flange operated switch (fusible or non-fusible)
  • Shaft:
    • 18.13" deep enclosures use DSFHS-17
    • 20.13" deep enclosures use DSFHS-22
    • 24.13" deep enclosures, platform must be used with shaft (not included)
  • Hhandle: DSFHN-HS12
 
Circuit breaker:
  • Circuit breaker: ABB
  • Operating mechanism
  • Shaft:
    • 18.13" deep enclosures use K7FHD-S17
    • 20.13" deep enclosures use K7FHD-S22
    • 24.13" deep enclosures, platform must be used with shaft (not included)
  • Handle mechanism: K7FHD-HS12
 
Allen Bradley
Bulletin 1494F flange mounted disconnect switch:
  • Disconnect switch
  • Fuse block adaptor (if required)
  • Line and load connectors (if required)
 
1494D flange mounted circuit breaker operating mechanism, order:
  • Circuit breaker: C-H Westinghouse
  • Flange mounted operating mechanism
  • Slide mechanism
 
Bulletin 1494U flange mounted disconnect switch, order:
  • Disconnect switch
  • Operating handle
  • Connecting rod/rods (long)
  • Trailer fuse block kit (if required)
  • Fuse kit (if required)
  • Line and load connectors (if required)
 
Bulletin 1494U flange mounted circuit breaker operating mechanism, order:
  • Circuit breaker: C-H Westinghouse
  • Operating mechanism
  • Operating handle
  • Connecting rod (long)
C-H Westinghouse
Type C361 disconnect switch:
  • Disconnect switch with an operating mechanism
  • Operating handle: C361H1 or C361H3
  • In 24.13" deep enclosures, platform must be used with shaft (not included)
 
Type C371 circuit breaker operating mechanism with a C-H Westinghouse circuit breaker:
  • Circuit breaker
  • Operating mechanism
  • Long operating rod (if required)
  • Operating handle:
    • 150 amp - C371H1 or C371H3
    • 250 through 1200 amp - C371H5 or C371H7
 
Flex-Shaft™ handle mechanism:
  • Circuit breaker
  • Complete Flex-Shaft™ handle mechanism
 
General Electric
Disconnect switch:
  • Disconnect switch: Type QMR or QMW
  • Fuse clip kit or no-fuse kit
  • Flange handle: STDA1 or STDA2
  • Variable depth operating mechanism
  • Extended length drive rod (if required)
 
Circuit breaker:
  • Circuit breaker
  • Flange handle: STDA1 or STDA2
  • Variable depth operating mechanism
  • Extended length drive rod (if required)
 
Circuit breaker with a Spectra-Flex™ cable operator:
  • Circuit breaker
  • Flange mounted handle mechanism:
    • 150 to 600 amps - STDA1
    • SK1200 - STDA3
  • Breaker mounted mechanism
  • Operating cable
I-T-E Siemens
Disconnect switch:
  • Basic switch (right-hand)
  • Fuse or no-fuse kit
  • Flange mounted handle: FHOHS
  • Switch operator
  • Operating cable FHOEC048
 
Circuit breaker:
  • Circuit breaker
  • Pressure wire connectors
  • Flange mounted handle:
    • 100 to 600 - FHOH
    • 800 to 2000 - FHOHN
  • Circuit breaker operator mechanism
  • Operating cable:
    • 18.13" deep or 24.13" deep enclosures accept 36" or 48" cables
    • 24.13" deep enclosures require a 48" cable 
  • These items are available from Siemens I-T-E as a complete mechanism with a 36" operating cable only Order items separately when using a 48" cable
 
Square D
Disconnect switch:
  • Disconnect switch with operating mechanism
  • Universal handle mechanism: Type A-1
  • Long operating rod (if required)
 
Circuit breaker:
  • Circuit breaker
  • Operating mechanism
  • Universal handle mechanism: Type A-1
  • Long operating rod (if required)
 
Class 9422 Type T disconnect switch with a cable mechanism:
  • Disconnect switch with operating mechanism: Class 9422, Type T
  • Handle mechanism: Class 9422, Type A-1
  • Cable mechanism: Class 9422 CFT_O, 3, 5, or 10 foot
 
Circuit breaker with a cable mechanism:
  • Circuit breaker: Square D
  • Handle mechanism: Class 9422, type A-1
  • Cable mechanism: Class 9422 CFT_O, 3, 5, or 10 foot
  ABB Controls

ABB Controls Disconnect Switches (Flange Mounted Operators)

Fits Enclosure Height ABB Switch 
Number
Amp 
Rating
Fuse Clip Fuse Class Space Occupied When 
A=72.13
P
When 
A=84.13
P
When 
A=90.13
P
72.13 84.13 90.13 L M
OETL-NF30-F 30A No Fuse 4.78 7.72 11.80 17.80 20.80
OETL-NF60-F 60A No Fuse 4.78 7.40 11.80 17.80 20.80
OETL-NF100-F 100A No Fuse 5.22 8.78 11.37 17.37 20.37
OETL-NF175-F 175A No Fuse 5.07 7.68 10.48 16.48 19.48
OETL-NF200-F 200A No Fuse 5.07 8.47 10.48 16.48 19.48
OESA-F30J6-F 30A 30A-600V J 4.78 7.72 11.80 17.80 20.80
OESA-F60J6-F 60A 60A-600V J 4.78 7.40 11.80 17.80 20.80
OESA-F100J6-F 100A 100A-600V J ¹ 5.22 8.78 11.37 17.37 20.37
        200A ²              
¹ J type fuse clips are standard. If 600 V Type “T” fuse clips are desired order T type fuse adaptor kit.
² 200 A available by using non-fusible 200A switch and a trailing fuse block. (consult ABB)   ABB Controls Circuit Breakers (Flange Mounted Operators)
Fits Enclosure Height ISOMAX Circuit
Breaker
Amp
Rating
Operating 
Mechanism
Frame
Type
Space Occupied When 
A=72.13
P
When 
A=84.13
P
When
A=90.13
P
72.13 84.13 90.13 L M
S1N100TL 100A K2FHD-M S1 5.30 4.57 12.33 18.33 21.33
S3N150TW 150A K3FHD-M S3 6.67 4.99 11.73 17.73 20.73
S3N225TW 225A K3FHD-M S3 6.67 4.99 11.73 17.73 20.73
S4N250BW 250A K4FHD-M S4 8.45 4.99 10.20 16.20 19.20
S5N400TW 400A K5FHD-M S5 8.45 6.37 10.20 16.20 19.20
S6N600TW 600A K6FHD-M S6 8.33 9.97 9.53 15.53 18.53
S6N800TW 800A K6FHD-M S6 8.33 9.97 9.53 15.53 18.53
"K" = 11.88 when "A" = 72.13
"K" = 17.88 when "A" = 84.13
"K" = 20.88 when "A" = 90.13 Charts reference Space Occupied by Disconnect Drawing.  

Allen Bradley

Allen Bradley 1494F Disconnect Switches
Fits Enclosure Height Allen Bradley
Type Number
Amp Rating Fuse Clip Fuse Class Space Occupied When 
A=72.13
P
When
A=84.13
P
When
A=90.13
P
72.13 84.13 90.13 L
N30 30A No Fuse 4.62 6.50 9.31 15.31 18.31
NF30 30A 30A-250V H, K, R 6.50 6.50 9.31 15.31 18.31
NF30 30A 60A-250V H, K, R 7.25 6.50 9.31 15.31 18.31
NF30 30A 30A-600V H, K, R 9.25 6.50 9.31 15.31 18.31
NF30 30A 60A-600V H, K, R 9.75 6.50 9.31 15.31 18.31
NF30 30A 30A-600V J 6.50 6.50 9.31 15.31 18.31
NF30 30A 60A-600V J 6.62 6.50 9.31 15.31 18.31
N60 60A No Fuse 4.62 6.50 8.62 14.62 17.62
NF60 60A 30A-600V H, K, R 10.38 6.50 8.62 14.62 17.62
NF60 60A 60A-250V H, K, R 8.38 6.50 8.62 14.62 17.62
NF60 60A 100A-250V H, K, R 10.88 6.50 8.62 14.62 17.62
NF60 60A 60A-600V H, K, R 10.88 6.50 8.62 14.62 17.62
NF60 60A 100A-600V H, K, R 12.88 6.62 8.62 14.62 17.62
NF60 60A 60A-600V J 7.75 6.50 8.62 14.62 17.62
NF60 60A 100A-600V J 9.75 6.50 8.62 14.62 17.62
N100 100A No Fuse 4.62 7.25 6.75 12.75 15.75
NF100 100A 100A-250V H, K, R 11.38 7.38 6.75 12.75 15.75
NF100 100A 200A-250V H, K, R 12.25 7.62 6.75 12.75 15.75
NF100 100A 100A-600V H, K, R 13.38 7.50 6.75 12.75 15.75
NF100 100A 200A-600V H, K, R 14.75 7.75 6.75 12.75 15.75
NF100 100A 100A-600V J 10.12 7.38 6.75 12.75 15.75
NF100 100A 200A-600V J 10.88 7.50 6.75 12.75 15.75
N200 200A No Fuse 7.12 10.38 5.12 11.12 14.12
NF200 200A 200A-250V H, K, R 15.00 10.38 5.12 11.12 14.12
NF200 200A 400A-250V H, K, R 16.56 10.75 5.12 11.12 14.12
NF200 200A 200A-600V H, K, R 17.56 10.38 5.12 11.12 14.12
NF200 200A 400A-600V H, K, R 19.56 11.00 5.12 11.12 14.12
NF200 200A 200A-600V J 13.69 10.38 5.12 11.12 14.12
NF200 200A 400A-600V J 15.00 10.62 5.12 11.12 14.12
¹"M" dimension does not allow for auxiliary switches. Refer to Allen Bradley instructions if additional space is required.   Allen Bradley 1494D Operators (Circuit Breakers)
Fits Enclosure Height Alan Bradley
Type Number
Amp 
Rating
Circuit Breker Type Space Occupied When 
A=72.13
P
When 
A=84.13
P
When 
A=90.13
P
72.13 84.13 90.13 L
N4/N40 150A C-H Westinghouse EHD, FD, 
FDB, FDC, HFD, HMCP
5.81 4.56 9.25 15.25 18.25
N5/N50 250A C-H Westinghouse JD, JDB, 
JDC, HJD, HMCP
8.81 4.75 8.44 14.44 17.44
N5/N60 400A C-H Westinghouse KD, KDB,
DK, HKD, HMCP
8.81 5.88 8.50 14.50 17.50

1 "M" dimension does not allow for auxiliary switches. Refer to Allen Bradley instructions if additional space is required.

"K" = 9.88 when "A" = 72.13 (except 200A switch) "K" = 8.56 when "A" = 72.13 (200A switch)
"K" = 15.88 when "A" = 84.13 (except 200A switch) "K" = 14.56 when "A" = 84.13 (200A switch)
"K" = 18.88 when "A" = 90.13 (except 200A switch) "K" = 17.56 when "A" = 90.13 (200A switch)

Charts reference Space Occupied by Disconnect Drawing.  

Allen Bradley 1494U Operators (Disconnect Switches)

Fits Enclosure Height Allen Bradley Switch 
Number
Amp 
Rating
    Space Occupied When 
A=72.13
P
When 
A=84.13
P
When 
A=90.13
P
72.13 84.13 90.13 Fuse Clip Fuse Class L
DS30 30A No Fuse 3.88 6.75 10.00 16.00 19.00
DS30 30A 30A-250V H,K,R 5.25 6.75 10.00 16.00 19.00
DS30 30A 30A-600V H,K,R 8.00 6.75 10.00 16.00 19.00
DS30 30A 30A-600V J 5.25 6.75 10.00 16.00 19.00
DS30 30A 60A-250V H,K 6.00 6.75 10.00 16.00 19.00
DS30 30A 60A-600V H,K 8.50 6.75 10.00 16.00 19.00
DS30 30A 60A-600V J 5.38 6.75 10.00 16.00 19.00
DS60 60A No Fuse 3.88 6.75 9.81 15.81 18.81
DS60 60A 60A-250V H,K,R 6.00 6.75 9.81 15.81 18.81
DS60 60A 60A-600V H,K,R 8.50 6.75 9.81 15.81 18.81
DS60 60A 60A-600V J 5.38 6.75 9.81 15.81 18.81
DS60 60A 30A-600V H,K,R 8.00 6.75 9.81 15.81 18.81
DS60 60A 100A-250V H,K 8.50 6.75 9.81 15.81 18.81
DS60 60A 100A-600V H,K 10.50 6.75 9.81 15.81 18.81
DS60 60A 100A-600V J 7.25 6.75 9.81 15.81 18.81
DS100² 100A No Fuse 3.88 6.75 9.81 15.81 18.81
DS100² 100A 100A-250V H,K,R 8.12 6.75 9.81 15.81 18.81
DS100² 100A 100A-600V H,K,R 10.12 6.75 9.81 15.81 18.81
DS100² 100A 100A-600V J 6.80 6.75 9.81 15.81 18.81
DS100² 100A 60A-600V H,K,R 10.12 6.75 9.81 15.81 18.81
DS100² 100A 60A-600V J 8.88 6.75 9.81 15.81 18.81
DS200² 200A No Fuse 4.75 8.00 8.34 14.34 17.34
DS200² 200A 200A-250V H,K,R 10.88 8.00 8.34 14.34 17.34
DS200² 200A 200A-600V H,K,R 13.88 8.00 8.34 14.34 17.34
DS200² 200A 200A-600V J 9.50 8.00 8.34 14.34 17.34
DS200² 200A 100A-600V H,K,R 12.00 8.00 8.34 14.34 17.34
DS200² 200A 100A-600V J 8.75 8.00 8.34 14.34 17.34
  DS400 400A No Fuse 10.75 11.00   10.14 13.14
  DS400 400A 400A-250V H,K,R 16.12 11.00   10.14 13.14
  DS400 400A 400A-600V H,K,R 19.12 11.00   10.14 13.14
  DS400 400A 400A-600V J 14.62 11.00   10.14 13.14
    DS600 600A No Fuse 10.75 11.00     13.14
    DS600 600A 600A-250V H,R 10.75 11.00     13.14
    DS600 600A 600A-600V H,R 10.75 11.00     13.14
    DS600 600A 600A-600V J 17.59 11.00     13.14
1 Series B
2 "M" dimension does not allow for auxiliary switches
  Allen Bradley 1494U Operators (Circuit Breakers)
Fits Enclosure Height Allen Bradley 
Type Number
Amp Rating Frame Type Space Occupied When 
A=72.13
P
When 
A=84.13
P
When 
A=90.13
P
72.13 84.13 90.13 L
M40 15A-150A C-H Westinghouse 
EHD,FD,FDB,FDC,HFD,HMCP
5.00 4.62 11.25 17.25 20.25
M50 70A-250A C-H Westinghouse
JD,JDB,JDC,HJD,HMCP
9.75 4.88 10.81 16.81 19.81
M60 100A-400A C-H Westinghouse 
KD,KDB,DK,HKD,HMCP
9.69 6.25 10.62 16.62 19.62
1"M" dimension does not allow for auxiliary switches. Refer to Allen Bradley instructions if additional space is required.

"K" = 11.88 when "A" = 72.13
"K" = 17.88 when "A" = 84.13, except 400A or 600A switches
"K" = 20.88 when "A" = 90.13, except 400A or 600A switches
"K" = 16.43 when "A" = 84.13, 400A switches only
"K" = 19.43 when "A" = 90.13, 400A and 600A switches only

Charts reference Space Occupied by Disconnect Drawing.   Cutler Hammer

Cutler Hammer C361 Disconnect Switches
Fits Enclosure Height Cutler Hammer 
Type Number
Amp 
Rating
    Space Occupied When 
A=72.13
P
When 
A=84.13
P
When 
A=90.13
P
72.13 84.13 90.13 Fuse Clip Fuse Class L
C361NC 30A No Fuse 5.75 7.55 10.50 16.50 19.50
C361SC21 30A 30A-250V H, K, R 8.38 7.55 10.50 16.50 19.50
C361SC61 30A 60A-250V H, K, R 8.38 7.55 10.50 16.50 19.50
C361SC61 30A 30A-600V H, J, K, R 8.38 7.55 10.50 16.50 19.50
C361ND 60A No Fuse 5.75 7.55 10.50 16.50 19.50
C361SD22 60A 60A-250V H, K, R 8.38 7.55 10.50 16.50 19.50
C361SD22 60A 30A-600V J 8.38 7.55 10.50 16.50 19.50
C361SD62 60A 60A-600V H, K, R 8.38 7.55 10.50 16.50 19.50
C361SD62 60A 60A-600V J 8.38 7.55 10.50 16.50 19.50
C361NE 100A No Fuse 5.56 9.07 10.06 16.06 19.06
C361SE263 100A 100A-250V H, K, R 10.31 9.07 10.06 16.06 19.06
C361SE263 100A 100A-600V H, K, R 10.31 9.07 10.06 16.06 19.06
C361SE263 100A 100A-600V J 10.31 9.07 10.06 16.06 19.06
C361NF 200A No Fuse 13.06 10.12 8.06 14.12 17.12
C361SF264 200A 200A-250V H, K, R 13.06 10.12 8.06 14.12 17.12
C361SF264 200A 200A-600V H, K, R 13.06 10.12 8.06 14.12 17.12
1 "M" dimension does not allow for auxiliary switches. Refer to Cutler Hammer instructions if additional space is required.

"K" = 11.88 when "A" = 72.13
"K" = 17.88 when "A" = 84.13
"K" = 20.88 when "A" = 90.13   Cutler Hammer C371 Circuit Breaker (C-H Westinghouse Circuit Breakers)
Fits Enclosure Height Cutler Hammer 
Mechanisms
Amp 
Rating
  Space Occupied When
A=72.13
P
When 
A=84.13
P
When 
A=90.13
P
72.13 84.13 90.13 Frame Type L M
C371E 150A F Frame EHD,FDB,FD,HFD,FDC 6.00 5.62 11.62 17.62 20.62
C371E 150A F Frame HMCP 6.00 5.62 11.62 17.62 20.62
C371F 250A J Frame JDB,JD,HJD,JDC 8.94 8.12 11.44 17.44 20.50
C371F 250A J Frame HMCP 10.94 8.12 11.44 17.44 20.50
C371F 400A K Frame DK,KDB,KD,HKD 9.75 8.12 11.00 17.00 20.00
C371F 400A K Frame HMCP 9.75 8.12 11.00 17.00 20.00
C371G 600A L Frame LD,HLD,LDC 8.44 12.00 9.38 15.38 18.38
  C371G 600A L Frame HMCP 8.44 12.00 9.38 15.38 18.38
  C371K 800A M Frame MD,MDS 10.25 12.00 11.81 14.81
  ¹ C371K 1200A M Frame ND,HND,NDC 10.25 12.00 11.81 14.81
1 Wire bend space "P" does not allow cable sizes larger than 350 MCM in an 84.13" tall enclosure when 4 cables per terminal used.
Refer to NATIONAL ELECTRIC Code 2005 table 312-6(b) for details.
Wire bend space "P" is compatible with C-H Westinghouse breakers with TA1201NB1 terminals.

"K" = 11.88 when "A" = 72.13
"K" = 17.88 when "A" = 84.13
"K" = 20.88 when "A" = 90.13

Charts reference Space Occupied by Disconnect Drawing.

  Cutler Hammer Flex-Shaft™ Operator Mechanisms (C-H Westinghouse Circuit Breakers)
Complete Operator   Breaker Height "X" Breaker Width "Y"
Mechanisms Amp  Rating Frame Type (in inches) (in inches)
F1S03 150A F Frame EHD,FDB,FD,HFD 6.00 4.12
F1S03 150A F Frame HMCP 6.00 4.12
F2S03 250A J  Frame JDB,JD,HJD,JDC 10.00 4.12
F2S03 250A J  Frame HMCP 10.00 4.12
F3S03 400A K  Frame DK,KDB,KD,HKD 10.12 5.50
F3S03 400A K  Frame HMCP 12.45 5.50
F4S04 600A L  Frame LD,HLD,LDC 10.75 8.25
F4S04 600A L  Frame HMCP 12.50 8.25
F7S04 800A M Frame MD,MDS 16.00 8.25
F5S04 1200A N Frame ND,HND,NDC 16.00 8.25
F6S04 2500A R Frame RD,CRD, RDC 16.00 15.50
Part numbers for Complete Operator Mechanisms include flange mounted handle, flexible shaft and circuit breaker mechanism.
The last digit of the part number denotes the shaft length (F1S03=3' length).   
  • F,J,K frame Flex-Shafts™ available in 3' to 10' lengths.
  • L,N,R frame Flex-Shafts™ available in 4' to 6' lengths.
 


Space Occupied By Disconnect
1. Flex-Shaft™ System permits circuit breaker locations separate from flange mounted handle mechanism.
2. See National Electrical Code 2005 article 430-10(b) for wiring space (Ref “P”) required for line side conductors.
3. Select shaft length based on location of circuit breaker in the enclosure. Maintain a 4" minimum bending radius for the Flex-Shaft™.
4. Space occupied by circuit breaker is calculated by:

 
  • Overall (Height "X" and Width "Y")
  • Minimum wire bend space (manufacturer specified)
  • Location "M" from right to left.

Charts reference Space Occupied by Disconnect Drawing.

      General Electric 

General Electric Type STDA Disconnect Switch Operators  
Fits Enclosure Height General Electric 
Switch 
Mechanisms
Amp 
Rating
Fuse Clip Fuse Class Space Occupied When 
A=72.13
P
When
A=84.13
P
When 
A=90.13
P
72.13 84.13 90.13 L M
TDOM1A 30A No Fuse 6.88 5.38 12.38 18.38 21.38
TDOM1A 30A 30A-250V H, R 6.88 5.38 12.38 18.38 21.38
TDOM1B 30A 30A-600V H, R 11.50 5.38 12.38 18.38 21.38
TDOM1B 30A 60A-250V H, R 11.50 5.38 12.38 18.38 21.38
TDOM1B 30A 60A-600V H, R 11.50 5.38 12.38 18.38 21.38
TDOM1A 60A No Fuse 6.88 5.38 12.38 18.38 21.38
TDOM1B 60A 60A-250V H, R 11.50 5.38 12.38 18.38 21.38
TDOM1B 60A 60A-600V H, R 11.50 5.38 12.38 18.38 21.38
TDOM1B 60A 100A-250V H, R 11.50 5.38 12.38 18.38 21.38
TDOM1B 60A 100A-600V H, R 11.50 5.38 12.38 18.38 21.38
TDOM1A 100A No Fuse 6.88 5.38 12.38 18.38 21.38
TDOM1B 100A 100A-250V H, R 11.50 5.38 12.38 18.38 21.38
TDOM1B 100A 100A-600V H, R 11.50 5.38 12.38 18.38 21.38
TDOM1B 100A 200A-250V H, R 11.50 5.38 12.38 18.38 21.38
TDOM1B 100A 200A-600V H, R 11.50 5.38 12.38 18.38 21.38
TDOM2 200A No Fuse 7.00 9.25 9.69 15.69 18.69
TDOM2 200A 200A-250V H, R 15.38 9.25 9.69 15.69 18.69
TDOM2 200A 200A-600V H, R 15.38 9.25 9.69 15.69 18.69
      General Electric Type STDA Circuit Breaker Operators  
Fits Enclosure Height General Electric
Circuit Breaker
Mechanisms
Amp Rating Frame Type Space Occupied When 
A=72.13
P
When 
A=84.13
P
When 
A=90.13
P
72.13 84.13 90.13 L M
SDOM1A 150A TEB, TED, THED 6.88 5.38 11.24 17.24 20.24
SDOM1A 150A TEC 6.88 5.38 11.24 17.24 20.24
TDOM1B 150A TB1 11.50 5.38 11.24 17.24 20.24
TDOM1B 150A TEC, TECL 11.50 5.38 11.24 17.24 20.24
TDOM1C 150A TEL 6.88 5.38 11.24 17.24 20.24
TDOM1D 150A THLC1 6.88 5.38 9.87 15.87 18.87
TDOM3 225A TFJ 10.38 5.88 10.81 16.81 19.81
TDOM3 225A TFK, THFK, TFL 10.38 5.88 10.81 16.81 19.81
TDOM4 400A TJJ, TJK4, THJK4, TJL4V 8.25 9.50 9.91 15.91 18.91
TDOM4 600A TJK6, THJK6, TJ4V, TJL4V 8.25 9.50 9.91 15.91 18.91
TDOM5 400A TB4, TJH6S 14.25 9.50 9.91 15.91 18.91
  TDOM6 225A TLB2, THLC2 11.75 9.50 15.35 18.35
  TDOM6 400A TLB4, THLC4 11.75 9.50 13.97 16.97
    TDOM6 800/1200A TKMA, THKMA, TK4V 11.75 9.50 18.38
    TDOM6 1200A TK4BV, THK4V 11.75 9.50 18.38
  TDOM7 600A TB6 18.12 9.50 12.25 15.25
  TDOM7 800A TB8 18.12 9.50 12.25 15.25
    TDOM7 1200A TKL12S 18.12 9.50 15.25
SD0M1A 150A SE150 6.88 5.38 11.24 17.24 20.24
SD0M3 250A SPECTRA SF250 10.38 5.88 10.81 16.81 19.81
  SD0M4 600A SPECTRA SG600 10.00 7.12 13.18 16.18
 

"K" = 11.88 when "A" = 72.13
"K" = 17.88 when "A" = 84.13
"K" = 20.88 when "A" = 90.13

Charts reference Space Occupied by Disconnect Drawing.

      General Electric Circuit Breakers (Spectra-Flex™ Cable Operators)  
Fits Enclosure Height     Circuit Breaker Height Circuit Breaker Width
72.13 84.13 90.13 Max Frame Size Amp Rating "X" "Y"
E150 150A 6.31 4.12
SE150 150A 6.31 4.12
SF250 250A 10.12 4.12
SG600 600A 10.09 5.50
SK1200 1200A 15.50 8.25
Note: All 2HD & UHDM series enclosures that are 24.13" deep require a 48" or longer operating cable
 
Frame Size Breaker Mechanism Flange Mounting Handle¹ Operating Cable²
E150 SCOM1A SCH1 SC3L
SE150/SF250 SCOM1EF SCH1 SC3L
SG600 SCOM1G SCH1 SC3L
SK1200 SCOM1K SCH2k SC3H
1 Operating Cables are available 3' to 10' lengths.
2 In the table above, the number "3" in the part number indicates a 3' cable.

Space Occupied By Disconnect
1. GE Spectra-Flex™ Operating Cables permit circuit breaker locations separate from flange mounted handle mechanism.
2. See National Electrical Code 2005 article 430-10(b) for wiring space (Ref "P") required for line side conductors.
3. Select shaft length based on location of circuit breaker in the enclosure. Maintain a 3" minimum bending radius for the Flex-Shaft™.
4. Space occupied by circuit breaker is calculated by:

 
  • Overall (Height "X" and Width "Y")
  • Minimum wire bend space (manufacturer specified)
  • Location "M" from right to left.

"K" = 11.88 when "A" = 72.13
"K" = 17.88 when "A" = 84.13
"K" = 20.88 when "A" = 90.13

Charts reference Space Occupied by Disconnect Drawing.

      Siemens I-T-E 

I-T-E - Disconnect Switches (Max-Flex™ Operators)  
Fits Enclosure Height         Disconnect Height 
"X"
Disconnect Width 
"Y"
72.13 84.13 90.13 ITE Switch Type Amp Rating Fuse Clip Fuse Class
MCS603R 30A No Fuse 5.52 6.13
MCS603R 30A 30A-250V H,K,R 8.11 6.13
MCS603R 30A 30A-600V H,K,R 10.11 6.13
MCS603R 30A 30A-600V J 8.48 6.13
MCS606R 60A No Fuse 5.52 6.13
MCS606R 60A 60A-250V H,K,R 7.86 6.13
MCS606R 60A 60A-600V H,K,R 10.38 6.13
MCS606R 60A 60A-600V J 8.36 6.13
MCS610R 100A No Fuse 7.59 7.38
MCS610R 100A 100A-250V H,K,R 11.85 7.38
MCS610R 100A 100A-600V H,K,R 13.85 7.38
MCS610R 100A 100A-600V J 10.60 7.38
MCS620R 200A No Fuse 9.00 9.17
MCS620R 200A 200A-250V H,K,R 14.70 9.17
MCS620R 200A 200A-600V H,K,R 17.20 9.17
MCS620R 200A 200A-600V J 13.32 9.17

Note: Enclosures that are 24.13" deep require a 48" Max-Flex™ cable (minimum cable length).       Siemens I-T-E Max-Flex™ Operators (Circuit Breakers)  
Complete Operator 
Mechansim
Amp
Rating
Breaker Frame Size      
Circuit Breaker Type Circuit Breaker Height "X" Circuit Breaker Width "Y"
FHOE036 125A ED ED2, ED4, ED6, HED4, HED6 6.34 3.00
FHOE036 125A CED CED6 9.58 3.00
FHOF036 250A FD FXD6-A, FD6-A, HFD6, FXD6-ETJ, HHFD6, HHFXD6 9.50 4.50
FHOF036 250A CFD CFD6, CFD6-ETI 14.25 4.50
FHOJ036 400A, 600A JD, LD JXD2, LXD6, JD6, LD6, HJD6, HLD6, HHJD6, HHLD6, HHJXD6, HHLDX6, JXD6-ETI, LXD6-ETI 11.00 7.50
FHOJ036 400A, 600A CJD,CLD CJD6, CLD6, CJD6-ETI, CLD6-ETI 17.86 7.50
FHOLMO36 800A LMD LMD6, LMXD6, HLMD6, HLMXD6, LMXD6-ETI 16.00 9.00
FHON048 800A, 1200A MD, ND MD6, ND6, MXD6, NXD6,HMD6, HND6, HMXD6, HNXD6, CMD6, CND6, MXD6-ETI, CMD6-ETI 24.00 9.00
FHONO48 1600A, 2000A PD,RD PD6, RD6, PXD6, RXD6, HPD6, HRD6, HPXD6, HRXD6, CPD6 24.50 13.63

Circuit Breaker Size includes required base mounting block.
Last three digits of operator mechanism part number denote cable length in inches. 
24" deep enclosures require longer operating cables. Sold separately.

"K" = 11.88 when "A" = 72.13
"K" = 17.88 when "A" = 84.13
"K" = 20.88 when "A" = 90.13
(Deduct 1.45 inches from “K” for FHONO48 Operator mechanism for MD,ND,PD,RD Circuit Breakers)

Space Occupied By Disconnect
1. I-T-E Max-Flex™ System permits circuit breaker locations separate from flange mounted handle mechanism.
2. See National Electrical Code 2005 article 430-10(b) for wiring space (Ref “P”) required for line side conductors.
3. See Siemens I-T-E instructions for disconnect location limitations when using 36" or 48" Max-Flex™ cables.
4. Space occupied by circuit breaker is calculated by:

 
  • Overall (Height "X" and Width "Y")
  • Minimum wire bend space (manufacturer specified)
  • Location "M" from right to left.

Charts reference Space Occupied by Disconnect Drawing.

      Square D

Square D Class 9422 Variable Depth Disconnect Switches  
Fits Enclosure Height Square D 
Type Number
Amp
Rating
    Space Occupied When 
A=72.13
P
When 
A=84.13
P
When 
A=90.13
P
72.13 84.13 90.13 Fuse Clip Fuse Class L M
TCN-30 30A No Fuse 3.80 6.97 10.75 16.75 19.75
TCF-30 30A 30A-250V H, K, R 5.53 6.97 10.75 16.75 19.75
TCF-33 30A 30A-600V H, K, R 8.15 6.97 10.75 16.75 19.75
TCF-33 30A 60A-250V H, K, R 6.15 6.97 10.75 16.75 19.75
TCF-33 30A 30A-600V J 5.53 6.97 10.75 16.75 19.75
TDN-60 60A No Fuse 3.80 6.97 10.75 16.75 19.75
TDF-60 60A 30A-600V H, K, R 8.15 6.97 10.75 16.75 19.75
TDF-60 60A 60A-250V H, K, R 6.15 6.97 10.75 16.75 19.75
TDF-63 60A 60A-600V H, K, R 8.65 6.97 10.75 16.75 19.75
TDF-63 60A 60A-600V J 5.53 6.97 10.75 16.75 19.75
TEN-10 100A No Fuse 3.80 6.97 10.62 16.62 19.62
TEF-10 100A 100A-250V H, K, R 8.25 6.97 10.62 16.62 19.62
TEF-10 100A 100A-600V H, K, R 10.25 6.97 10.62 16.62 19.62
TEF-10 100A 100A-600V J 7.05 6.97 10.62 16.62 19.62
TEF-13 100A 200A-600V J 10.62 16.62 19.62
TC-1 30A No Fuse 5.75 6.12 9.88 15.88 18.88
TC-2 30A 30A-250V H, K, R 5.75 6.12 9.88 15.88 18.88
TC-3 30A 30A-600V H, K, R 7.75 6.12 9.88 15.88 18.88
TC-3 30A 60A-250V H, K, R 5.88 6.12 9.88 15.88 18.88
TC-3 30A 30A-600V J 5.75 6.12 9.88 15.88 18.88
TD-1 60A No Fuse 6.38 6.75 10.75 16.75 19.75
TD-2 60A 30A-600V H, K, R 8.50 6.75 10.75 16.75 19.75
TD-2 60A 60A-250V H, K, R 6.50 6.75 10.75 16.75 19.75
TD-3 60A 60A-600V H, K, R 9.00 6.75 10.75 16.75 19.75
TD-3 60A 60A-600V J 6.38 6.75 10.75 16.75 19.75
TE-1 100A No Fuse 4.75 8.50 10.50 16.50 19.50
TE-2 100A 100A-250V H, K, R 7.50 8.50 10.50 16.50 19.50
TE-2 100A 100A-600V H, K, R 9.50 8.50 10.50 16.50 19.50
TE-2 100A 100A-600V J 6.25 8.50 10.50 16.50 19.50
TE-3 100A 200A-600V J 13.75 8.50 10.50 16.50 19.50
TF-1 200A No Fuse 5.50 11.75 9.12 15.12 18.12
TF-2 200A 200A-250V H, K, R 11.50 11.75 9.12 15.12 18.12
TF-2 200A 200A-600V H, K, R 14.00 11.75 9.12 15.12 18.12
TF-2 200A 200A-600V J 10.12 11.75 9.12 15.12 18.12
TF-3 200A 400A-600V J 14.50 11.75 9.12 15.12 18.12
      Square D Class 9422 Variable Depth Operators (Circuit Breakers)  
Fits Enclosure Height Square D Type 
Number
Amp 
Rating
Frame Type Space Occupied When 
A=72.13
P
When 
A=84.13
P
When 
A=90.13
P
72.13 84.13 90.13 L M
RG-1 75A GJL 3.53 3.87 10.69 16.69 19.69
RG-1 100A GJL 3.53 3.87 10.69 16.69 19.69
RN-1 100A FAL, FHL 5.12 5.38 10.88 16.88 19.88
RP-1 250A KAL, KHL 7.12 5.75 11.56 17.56 20.56
  RR-1 400A LAL, LHL, Q4L 7.62 8.88 13.25 16.25
  RT-1 800A MEL, MXL 9.12 12.00 13.12 16.12
  RT-1 1000A MAL, MHL 9.12 12.00 13.12 16.12

"K" = 11.88 when "A" = 72.13
"K" = 17.88 when "A" = 84.13
"K" = 20.88 when "A" = 90.1

      Square D Class 9422 Disconnect Switches (Cable Mechanism 9422-CFT30 and 9422A-1 Handle Mechanism)  
Fits Enclosure Height Square D Type 
Number
Amp     Disconnect Height 
"X"
Disconnect Width 
"Y"
72.13 84.13 90.13 Rating Fuse Clip Fuse Class
TCN-30 30A No Fuse 5.90 6.20
TCF-30 30A 30A-250V H, K, R 7.50 6.20
TCF-33 30A 30A-600V H, K, R 10.15 6.20
TCF-33 30A 60A-250V H, K, R 8.15 6.20
TCF-33 30A 30A-600V J 7.50 6.20
TDN-60 60A No Fuse 5.90 6.20
TDF-60 60A 30A-600V H, K, R 10.15 6.20
TDF-60 60A 60A-250V H, K, R 8.15 6.20
TDF-63 60A 60A-600V H, K, R 10.65 6.20
TDF-63 60A 60A-600V J 7.50 6.20
TEN-10 100A No Fuse 5.90 6.20
TEF-10 100A 100A-250V H, K, R 10.35 6.20
TEF-10 100A 100A-600V H, K, R 10.35 6.20
TEF-10 100A 100A-600V J 10.35 6.20

Use switch with appropriate cable mechanism and 9422A-1 handle mechanism       Square D Class 9422 Cable Mechanism (Circuit Breakers)  
Fits Enclosure Height   Amp   Circuit Breaker Circuit Breaker
72.13 84.13 90.13 Cable Type Switch Rating Frame Type Height "X" Width "Y"
9422 CGJ30 75A GJL 4.75 3.50
9422 CEJ30 100A GJL 4.75 3.50
9422 CFA30 100A FAL, FHL 6.00 4.50
9422 CKA30 250A KAL, KHL 8.00 4.50
9422 CLA30 400A LAL, LHL,Q4L 11.00 6.00

Use cable mechanism with circuit breaker and 9422-A1 handle mechanism
Cable operators are offered in 3’, 5’, and 10’ lengths. Last 2 digits of part numbers above (30) are for 3’ cables

Space Occupied By Disconnect Switch
1. Square D Cable System permits circuit breaker locations separate from flange mounted handle mechanism.
2. See National Electrical Code 2005 article 430-10(b) for wiring space (Ref "P") required for line side conductors.
3. Select cable mechanism length based on disconnect location in enclosure. See Square D instructions for minimum cable bend radius.
4. Space occupied by circuit breaker is calculated by:

 
  • Overall (Height "X" and Width "Y")
  • Minimum wire bend space (manufacturer specified)

"K" = 11.88 when "A" = 72.13
"K" = 17.88 when "A" = 84.13
"K" = 20.88 when "A" = 90.13

Charts reference Space Occupied by Disconnect Drawing.